User Manual, Firmware rev. 3.0 or LATER Owner's manual

50 Publication 1404-UM001F-EN-P - November 2009
Chapter 3 Powermonitor 3000 Unit Operations
Advanced Device Configuration
A number of parameters are grouped into Advanced Configuration,
including the Password, demand and projected demand setup, relay
and KYZ pulse operation setup, metering accuracy options, date/time
and display module scrolling rate. To perform advanced configuration
by using the display module, navigate through these menus: PROG. >
PASS? > CONFIGURATION > ADVANCED. You may also set the
advanced device configuration via communication by writing to the
Advanced Device Configuration
table.
Password
The password protects the unit against unauthorized commands or
configuration changes. Be sure to write down the new password and
keep it in a safe place. Range 0…9999, default 0000.
TIP
If you forget or lose your password, contact Rockwell Automation
Technical Support for assistance. Refer to Rockwell Automation
Support on the back cover of this manual.
Device Configurations Summary
Parameter Range Default User Setting
Basic Configuration
Wiring Mode 0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT
5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo
6 = Wye
PT Primary
1
10,000,000
480
PT Secondary
1
600
480
CT Primary
1
10,000,000
5
CT Secondary
1
5
5
I4 Primary
1
10,000,000
5
I4 Secondary
1
5
5
Nominal System Voltage
(M6 and M8 only)
1
10,000,000
480