User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 261
Powermonitor 3000 Data Tables Appendix A
Controller Command Parameters
CSP File No. N53
Remote I/O BT -
CIP Assy. Inst. 67
No. of Elements 1
User Configurable No
Data Type Integer
Data Access Write only
PM3000 Type Ethernet
Controller Command
Element
No.
Element Name Range Default
Value
Comment
0 Controller Command
Bits 0
0…32,767 0 Refer to
Network Demand / Time
Configuration on page 55
Daylight Saving Time Configuration Parameters
CSP File No. N54
Remote I/O BT 47
CIP Assy. Inst. 68 (Write), 69 (Read)
No. of Elements 10
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Daylight Saving Time Configuration
Element
No.
Modbus
Address
Element name Range Default Comment
0 42101 Password -1…9999 0 Required for configuration. Returns -1
1 42102 DST Enable 0…1 0 0 = Disabled, 1 = Enabled
2 42103 DST Start Month 1…12 3 1 = January, 2 = February…
3 42104 DST Start Day 0…6 0 0 = Sunday, 1 = Monday…
4 42105 DST Start Day Instance 1…5 2 1 = 1st, 2 = 2nd, ... 5 = Last
5 42106 DST Start Hour 0…23 2 0 = 12:00 midnight, 1 = 1:00 AM…
6 42107 DST End Month 1…12 11 1 = January, 2 = February…
7 42108 DST End Day 0…6 0 0 = Sunday, 1 = Monday…
8 42109 DST End Day Instance 1…5 1 1 = 1st, 2 = 2nd, ... 5 = Last
9 43110 DST End Hour 0…23 2 0 = 12:00 midnight, 1 = 1:00 AM…