User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 19
Product Description Chapter 2
DeviceNet Optional Communication
A catalog number ending in -DNT specifies a power monitor with a
DeviceNet port in addition to the native RS-485 port. The DeviceNet
option permits concurrent use of both communication ports. The
DeviceNet port has the following performance features:
Adapter class device
Four communication rate settings: 125, 250, 500 Kbps, and
AutoBaud
Remotely settable communication rate
Cable length up to 500 m (1640 ft) maximum
Node capacity up to 64 nodes including master
Remotely settable node address
Shielded twisted-pair media containing both signal and power
conductors
Update rates for I/O channel: 100 ms minimum
Update rates for explicit messaging: 250 ms minimum
Configurable I/O channel assembly instance: six parameters
default, twenty-three maximum
Configurable explicit assembly instance: seventeen parameters
default, twenty-three parameters maximum
Explicit assembly instances for access to all data
Twenty-three single-instance parameters
Two I/O assembly instances
May be reset remotely through Identity Object
Support for up to four concurrent clients
Supports DeviceNet heartbeat facility
Ethernet Optional Communication
A catalog number ending in -ENT specifies a power monitor with one
active 10/100BaseT Ethernet communication port in addition to the
native RS-485 port. The Ethernet port has the following performance
features:
Connect to PLC-5E, SLC 5/05, ControlLogix Ethernet Bridge
controllers, and the 1761-NET-ENI module products
Built-in Internet Web page support
Compatible with RSPower, RSPowerPlus, RSEnergyMetrix, and
RSView32 software
Ethernet communication rate: 10/100 Mbps