User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 111
Communication Chapter 4
7. Select 3 as the Configuration instance and leave its Size set to 0
bytes and click the Next.
8. Set the Requested Packet Interval to 100 ms or greater.
The power monitor does not respond reliably to an RPI of less
than 100 ms.
Requested Packet Interval Setup
The power monitor data is found in controller tags.
Power Monitor I/O Tags