Installation Instructions, PRIOR to Firmware rev. 3.0 Manual

Publication 1404-IN007D-EN-P - October 2004
40 Powermonitor 3000
Figure 31 RS-485 Connections
150
Terminating
Resistor
(See Note 2)
150
Terminating
Resistor
(See Note 2)
Shield Connection
(See Note 4)
IBM Compatible PC
Or
PLC Processor
Or
SLC Processor
Or
ControlLogix Processor
Notes:
1) 3-device network portrayed. Up to 31 DF1
Slave Devices can be connected to a
DF1 Master without the use of a repeater
2) Terminating resistors may be required for
networks with long distances or high noise
environments. Consult the RS-232 to RS-485
converter manufacturer for more information.
3) Examples:
B & B Electronics
Part Number 485SD9TB (DB9).
Allen-Bradley Cat. 1761-NET-AIC.
4) Shields should be connected at
one end only to avoid ground loops.
Powermonitor 3000 Device #1
Powermonitor 3000 Device #2
Powermonitor 3000 Device #3 (Last)
RS-485
RS-485
RS-485
External
RS-232C to RS-485
Converter
(See Note 3)
SHLD
SHLD
_
+
SHLD
_
+
SHLD
_
+
A
B