Installation Instructions, PRIOR to Firmware rev. 3.0 Manual
Publication 1404-IN007D-EN-P - October 2004
14 Powermonitor 3000
Table 12 Ethernet/IP Optional Communications (Series B catalog numbers ending
in -ENT)
LED LED Color LED State and Communications
Condition
LNK Off No valid physical Ethernet connection
Steady Green Valid physical Ethernet connection
ACT Strobing or
Solid Yellow
Powermonitor 3000 transmitting onto
Ethernet
F1 Off Not Used
F2 Off Not Used
NETWORK STATUS Off No power
Flashing Green No established connections
Steady Green Connected; has at least one established
connection
Flashing Red Connection timeout; one or more
connections to this device has timed-out
Steady Red Duplicate IP; the IP address assigned to this
device is already in use
Flashing Green/Red Selftest; this device is performing a
power-up self test
Table 13 ControlNet Optional Communications (catalog numbers ending in -CNT)
LED LED Color LED State and Communications
Condition
CHAN A and
CHAN B
Off No power or Channel disabled
Steady Red Faulted unit
Alternating
red/green
Self-test
Alternating red/off Incorrect node configuration
Steady green Normal operation
Flashing green/off Temporary errors or node is not configured
to go on-line
Flashing red/off Media fault or no other nodes present on
network
Flashing red/green Incorrect network configuration
Status Off Normal operation
Flashing green Communication card power-up self-test
F1
LNK
ACT
F2
NETWORK
STATUS
Powermonitor 3000
CHAN A
CHAN B
NETWORK
STATUS
Powermonitor 3000