Installation Instructions, PRIOR to Firmware rev. 3.0 Manual
Publication 1404-IN007D-EN-P - October 2004
Powermonitor 3000 13
Table 10 DeviceNet Optional Communications (catalog numbers ending in -DNT)
LED LED Color LED State and Communications
Condition
F1 Off Not Used
F2 Off Not Used
NETWORK STATUS Off Power is off or the Powermonitor 3000 is
not online
Flashing Green Network status is OK, no connections
established
Steady Green Network status is OK, connections
established
Flashing Red Recoverable communications failure; port is
restarting
Steady Red Non-recoverable communications error;
check wiring and configuration parameters
Table 11 Ethernet Optional Communications (Series A catalog numbers ending in
-ENT)
LED LED Color LED State and Communications
Condition
LINK Off Ethernet connection is inactive
Steady Green Ethernet connection is active
RX Off Ethernet is idle, no active data present on
port
Flashing Red Active data is present on Ethernet port
TX Off Powermonitor 3000 is not transmitting any
data through the Ethernet port
Flashing Red Powermonitor 3000 is transmitting data
Powermonitor 3000
F1
F2
NETWORK
STATUS
Powermonitor 3000
LINK
RX
TX