Installation Instructions, PRIOR to Firmware rev. 3.0 Manual
Publication 1404-IN007D-EN-P - October 2004
Powermonitor 3000 11
The Display Module is shipped with a 3-meter (10 ft) long, shielded
4-pair cable that provides power and serial communications between
the Master Module and the Display Module. The Display Module fits
into a standard ANSI four inch analog meter cutout for panel
mounting. Only one Display Module may be connected to a Master
Module, although you may use one Display Module to configure and
monitor any number of Master Modules; one at a time.
Figure 4 Display Module
LED Indicators
The Powermonitor 3000 is equipped with six bi-color light emitting
diodes (LED’s) arranged as shown in
Figure 5.
Figure 5 LED Indicators
The three LED’s on the left display the same information on
Powermonitor 3000 modules with any communication option
including native RS-485 communications only. The three LED’s on the
right have different labels and different indications depending on the
communications option selected, as shown in the charts below.
Powermonitor 3000
RX
TX
RS-485
MODULE
STATUS
Table 6 LED Indicators All Powermonitor 3000 Models
LED LED Color LED State and Communications
Condition
Module Status Off Control power is off or insufficient
Steady Red Major fault; internal self-test has failed. If a
power cycle does not correct the problem,
call customer support
Steady Green Powermonitor 3000 is operating normally
RS-485 RX Off The RS-485 bus is idle; no active data is
present
Flashing Green Active data is present on the RS-485 bus
RS-485 TX Off Powermonitor 3000 is not transmitting data
onto the RS-485 bus
Flashing Green Powermonitor 3000 is transmitting data
onto the RS-485 bus