B–18 Smart Communication Card Data Tables
Publication
1403-5.1
Harmonic
Distortion T
ables – Read
Harmonic Distortion Data Tables for Channel 2 through Channel 7 are identical to the Even and Odd Harmonic
Distortion Tables for Channel 1. There are a total of 14 tables for this information.
(V1, V2, V3, I1, I2, I3, I4) The table sizes indicate this is Harmonic Distortion Data. The Channel Number designates
which one.
Table B.17 Even Harmonic Distortion Table – Channel 1
Parameter No. Parameter Name Master Module Range Word No. Range
13.1 IEEE Total Harmonic Distortion 0 to 1000% 1 0 to 9999
2
10
±
0
to
21
13.2 IEC Total Harmonic Distortion 0 to 1000% 3 0 to 9999
4
10
±
0
to
21
13.3
Meets IEEE 519
(Reserved 1403-LM)
–1 = Unknown
0 = Fail
1 = Pass
5 –1 to +1
13.4 TIF 0 to 9999x10
21
6 0 to 9999
(Reserved 1403-LM) 7
10
±
0
to
21
13.5 Crest Factor 0 to 9999x10
21
8 0 to 9999
(Reserved 1403-LM) 9
10
±
0
to
21
13.6 K-Factor 0 to 9999x10
21
10 0 to 9999
(Reserved 1403-LM) 11
10
±
0
to
21
13.7 Channel Number
1 = L1 Voltage
2 = L1 Current
3 = L2 Voltage
4 = L2 Current
5 = L3 Voltage
6 = L3 Current
7 = L4 Current
12 1 to 7
13.8 Harmonic Distortion – Fundamental 0 to 1000% 13 0 to 9999
(Reserved 1403-LM) 14
10
±
0
to
21
13.9 Harmonic Distortion – Second 0 to 1000% 15 0 to 9999
(Reserved 1403-LM) 16
10
±
0
to
21
13.10 Harmonic Distortion – Fourth 0 to 1000% 17 0 to 9999
(Reserved 1403-LM) 18
10
±
0
to
21
13.11 Harmonic Distortion – Sixth 0 to 1000% 19 0 to 9999
(Reserved 1403-LM) 20
10
±
0
to
21
13.12 Harmonic Distortion – Eighth 0 to 1000 % 21 0 to 9999
(Reserved 1403-LM) 22
10
±
0
to
21
13.13 Harmonic Distortion – Tenth 0 to 1000% 23 0 to 9999
(Reserved 1403-LM) 24
10
±
0
to
21
13.14 Harmonic Distortion – Twelfth 0 to 1000% 25 0 to 9999
(Reserved 1403-LM) 26
10
±
0
to
21
13.15 Harmonic Distortion – Fourteenth 0 to 1000% 27 0 to 9999
(Reserved 1403-LM) 28
10
±
0
to
21
13.16 Harmonic Distortion – Sixteenth 0 to 1000% 29 0 to 9999
(Reserved 1403-LM) 30
10
±
0
to
21
13.17 Harmonic Distortion – Eighteenth 0 to 1000% 31 0 to 9999
(Reserved 1403-LM) 32
10
±
0
to
21
13.18 Harmonic Distortion – Twentieth 0 to 1000% 33 0 to 9999
(Reserved 1403-LM) 34
10
±
0
to
21