Table B.11 Event Log – Read
Parameter No. Parameter Name Master Module Range Word No. Range
8.1 Event Time Log Stamp Year 1
0–99
16 Bit Integer
Month, Date 2
1–12
8 Bit
1–31
8 Bit
Hour, Minute 3
0–23
8 Bit
0–59
8 Bit
Seconds, Hundredths 4
0–59
8 Bit
0–99
8 Bit
8.2 Event Type Value 0 to 14 5 0 to 14
8.3 Event Code Value 0 to 10 6 0 to 10
8.4 Setpoint Type 0 to 54 7 0 to 54
8.5 Setpoint Evaluation Condition 0 to 5 8 0 to 5
8.6 Setpoint Level
±
9999x10
21
9
±
0 to 9999
10
10
±
0
to
21
8.7 Setpoint Action/Release Delay 0 to 9999 11 0 to 9999
8.8 Setpoint Action 0 to 20 12 0 to 20
8.9 Number of Event Logs Requested 1 to 100 13 1 to 100
8.10 Number of Event Log Received (Counter) 1 to 100 14 1 to 100
8.11 Number of Event Log Being Returned 1 to 100 15 1 to 100
8.12 Internal Identifier –32767 to +32767 16 –32767 to +32767
Reserved Word 17
Reserved Word 18
Reserved Word 19
Reserved Word 20
Reserved Word 21
Reserved Word 22
8.13 Data Format
0 = Integer/Exponent
1 = Floating Point
23 0 to 1