Instruction Sheet User guide
B–4 Smart Communication Card Data Tables
Publication
1403-5.1
Table B.3 Smart Communication Card Data Table – Write and Read
Note: The device will not respond to a broadcast of this table.
Parameter
No.
Parameter Name Master Module Range PLC Word No. Range
2.1 R I/O Rack Address 0 to 63 1 0 to 63
2.2 R I/O Group Number 0 to 6 2 0 to 6
2.3 R I/O Last Rack
0 = No – Default
1 = Yes
3 0 to 1
2.4 R I/O Baud Rate
0 = 56K – Default
1 = 115K
2 = 230K
4 0 to 2
2.5 Serial Response Delay 0 to 15 5 0 to 15
2.6 Serial Type Specifier RS-232 or RS-485
0 = RS-485
1 = RS-232 – Default
6 0 to 1
2.7 SCC RS-232/RS-485 Baud Rate
0 = 1200
1 = 2400
2 = 4800
3 = 9600 – Default
4 = 19200
7 0 to 4
2.8 Serial Device Identifier 0 to 255 8 0 to 255
2.9 R I/O Port Data Format
0 = Integer/Exponent
1 = Floating Point
9 0 to 1
2.10 Serial Port Data Format
0 = Integer/Exponent
1 = Floating Point
10 0 to 1
2.11 Reserved 11
2.12 Reserved 12
2.13 Reserved 13
2.14 Reserved 14
2.15 Reserved 15
2.16 Reserved 16
2.17 Reserved 17
2.18 Reserved 18
2.19 Reserved 19
2.20 Reserved 20
2.21 Present Unit Password
–1 is always returned for a Read
0 to 9999 is required for a Write
21 –1 to +9999
Reserved 22
Reserved 23
Reserved 24
Reserved 25
Reserved 26
Reserved 27
Reserved 28
Reserved 29
Reserved 30