Installation Instructions Manual

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-61
Instance 55 Attribute (Snapshot 1 parameter record)
Assembly Structure
Configurable channel parameter list
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
3 Get Data Structure of
28 bytes; 14 words
Note: this table is only supported when master module
firmware is V3.00 or later
Param
#
Parameter name Data
Typ e
# bytes Description Word
No.
1 The value of user selected parameter #1
Refer to parameter 9, Instance 23.
Float 4 Range depends on the selected parameter 1
2
2 Record Timestamp; Year Int 8 Year 3
Record Timestamp; Month, Day Int Month = Value/256
Day = Remainder of Value/256
4
Record Timestamp; Hour, Minute Int Hour = Value/256
Minute = Remainder of Value/256
5
Record Timestamp; Seconds, hSeconds Int Seconds = Value/256
Hseconds = Remainder of Value/256
6
3 Snashot record # being returned Int 2 Range 1 to 1861 7
4 Unused Int 2 0 8
Param # Parameter name Data type #bytes Comment
0 None Int 2 If this parameter is selected, a fixed 0 integer is returned
1 Relay #1 status Int 2 See Instance 1, parameter 1
2 Relay #2 status Int 2 See Instance 1, parameter 2
3 Alarm word Int 2 See Instance 1, parameter 3
4 Status inputs Int 2 See Instance 1, parameter 4
5 Voltage mode Int 2 See Instance 6, parameter 3
6 Vaux voltage mode Int 2 See Instance 6, parameter 4
7 L1/L1/L3 PT primary Float 4 See Instance 6, parameter 5
8 L1/L2/L3 PT secondary Float 4 See Instance 6, parameter 6
9 I1/I2/I3 CT primary Float 4 See Instance 6, parameter 7
10 I1/I2/I3 CT secondary Float 4 See Instance 6, parameter 8
11 I4 CT primary Float 4 See Instance 6, parameter 9
12 I4 CT secondary Float 4 See Instance 6, parameter 10
13 Vaux PT primary Float 4 See Instance 6, parameter 11
14 Vaux PT secondary Float 4 See Instance 6, parameter 12