Installation Instructions Manual

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-57
Instance 51 Attribute (Snapshot 16 parameter record; table 2 of 2)
Assembly Structure
7 L4 Current Float 4 RMS current measured via the I4+/I4- terminals 13
Range = 0 to 9999x10
21
Amps
14
8 Voltage Unbalance Float 4 Range = 0.0 to 100% 15
16
9 Current Unbalance Float 4 Range = 0.0 to 100% 17
18
10 Record Timestamp; Year Int 8 Year 19
Record Timestamp; Month, Day Int Month = Value/256
Day = Remainder of Value/256
20
Record Timestamp; Hour, Minute Int Hour = Value/256
Minute = Remainder of Value/256
21
Record Timestamp; Seconds, hSeconds Int Seconds = Value/256
Hseconds = Remainder of Value/256
22
11 Snashot record # being returned Int 2 Range 1 to 265 23
12 Unused Int 2 0 24
Param
#
Parameter name Data
Typ e
# bytes Description Word
No.
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
3 Get Data Structure of
40 bytes; 20 words
Note: this table is only supported when master module
firmware is V3.00 or later
Param
#
Parameter name Data
Typ e
# bytes Description Word
No.
1 Total Real Power Float 4
Range = 0 to 9999x10
21
W
1
2
2 Total Reactive Power Float 4
Range = 0 to 9999x10
21
VAR
3
4
3 Demand W Float 4
Range = 0 to 9999x10
21
W
5
6
4 Demand VAR Float 4
Range = 0 to 9999x10
21
VAR
7
8
5 Total True PF Float 4 Range = -100 to 100% 9
10
6 Wh net Float 4
Range = -9999 x10
21
to 9999x10
21
Wh
11
12