Installation Instructions Manual

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-53
Common Services
Instance 47 Attributes (Minimal power assembly for demand
profiling)
Assembly Structure
5 L1 L2 L3 frequency (10-cycle
average)
Float 4 20.0 to 132.0 9
10
6 Phase rotation Int 2 0 = No Rotation
1 = ABC
2 = ACB
11
7 Metering iteration Int 2 Used by external device to determine if it
has new metering data. Counts from 0 to
32767, then rolls over to 0.
12
Param # Parameter name Data
type
#bytes Master Module Range Word
No.
Service
Code
Service Name
0Ehex Get_Attributes_Single
Attribute ID Access
Rule
Name DeviceNet Data Type
3 Get Data Structure of
34 bytes (17 Words)
Param # Parameter name Data
type
#bytes Master Module Range Word No.
1 Total real power Float 4
0.0 to 9999x10
21
W
1
2
2 Total reactive power Float 4
0.0 to 9999x10
21
VAR
3
4
3 Total apparent power Float 4
0.0 to 9999x10
21
VA
5
6
4 Demand current Float 4
0.0 to 9999x10
21
amps
7
8
5 Demand power Float 4
0.0 to 9999x10
21
W
9
10
6 Demand reactive power Float 4
0.0 to 9999x10
21
VAR
11
12
7 Demand apparent power Float 4
0.0 to 9999x10
21
VA
13
14
8 Elapsed time Float 4
0.0 to 9999x10
21
15
16
9 Metering iteration Int 2 Used by external device to determine if it
has new metering data. Counts from 0 to
32767, then rolls over to 0.
17