Installation Instructions Manual

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-45
Assembly Structure
Common Services
Param # Parameter name Data
type
#bytes Master Module Range Default
Setting
Word
No.
1 Password Int 2 -1, 0 to 9999
Correct password is required to
configure/reconfigure harmonic Analysis
functionality, but not required to select
harmonic channel or data group to be read back
in the harmonic results data assembly. If the
user is only selecting harmonic result data to be
read, set password to1.
01
2 Harmonic channel
to be read
Int 2 1 = L1 Voltage
2 = L1 Current
3 = L2 Voltage
4 = L2 Current
5 = L3 Voltage
6 = L3 Current
7 = L4 Current
2
3 Read % distortion,
magnitude, or phase
angle data
Int 2 Selects which type of data appears in Instance
39 through Instance 43 (% distortion of
harmonic, magnitude of harmonic, or phase
angle of harmonic). 0 = % distortion, 1 =
magnitude, 2 = phase angle.
3
4 Reserved Int 2 Reserved for future enable/disable of all
harmonic calculations.
4
5 IEEE 519 max short
circuit current
Float 4 0.0 to 10,000,000.0 0 5
6
6 IEEE 519 max
demand/load
current
Float 4 0.0 to 10,000,000.0 0 7
8
Service
Code
Service Name
10
hex Set_Attributes_Single