Installation Instructions Manual
Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-13
Instance 9 Attributes (DeviceNet Communication Configuration
Write)
(1)
Assembly Structure
Common Services
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
3 Set Data Structure of
10 bytes (5 Words)
(1) Attempts to write node address of 64 or baud rate of 3 (Autobaud) or 4 (Program baud) with serial
communications will be inhibited for the DeviceNet V1 communication cards.
Param # Parameter name Data type #bytes Master Module Range Default
Setting
Word
No.
1 Password Int 2 0 to 9999 required 0 1
2 Node address Int 2 0 to 63 (DeviceNet V1)
0 to 64 (DeviceNet V2)
(1)
63 2
3 Baud rate Int 2 0 = 125k
1 = 250k
2 = 500k
3 = Auto (DeviceNet V2 only)
4 = Programmable (DeviceNet V2 only)
125k bps 3
4 Bus off interrupt Int 2 Action to take when a BOI occurs:
0: hold CAN chip in reset
1: reset CAN chip and continue
communicating
04
5 Reserved Int 2 0 5
(1) Node address 64 enables remote node address programming; there is no actual node address of 64 defined for DeviceNet.
Service
Code
Service Name
10
hex Set_Attributes_Single