Installation Instructions Manual

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-11
Common Services
nstance 8 Attributes (Advanced Configuration Data Read)
Assembly Structure
18 Set VAR hours Float 4
–9999x10
8
to +9999x10
8
Set to -1.0 for no effect on var-hour
counter.
19
20
19 Set time/date 4 word 8 Year 21
Month, Day 22
Hour, Minute 23
Seconds, Hundredths 24
(1) On a read, returns the value of the status input counter.
Param # Parameter name Data type #bytes Master Module Range Default
Setting
Word
No.
Service
Code
Service Name
10
hex Set_Attributes_Single
Attribute ID Access
Rule
Name DeviceNet Data Type
3 Get Data Structure of
48 bytes (24 Words)
Param # Parameter name Data type #bytes Master Module
Range
Default
Setting
Word No.
1 Unused Int 2 Same size as write
for
read/modify/write of
assembly.
1
2 Demand period length Int 2 99 to +99 1 2
3 Number of demand periods Int 2 1 to 15 1 3
4 Output pulse relay # Int 2 0 = None
1 = Relay 1
2 = Relay 2
04
5 Output pulse parameter Int 2 0 = kWh Forward
1 = kWh Reverse
2 = kVarh Forward
3 = kVarh Reverse
05
6 Output pulse increment Int 2 1 to 32766 1 6
7 Output pulse width Int 2 40 to 2000 100 7
8 Filter mode (1403-MM) or
Enable THD (1403-LM)
Int 2 0 or 1 1 8
9 Unused Int 2 Returns 0 9
10 Unused Int 2 Returns 0 10
11 Unused Int 2 Returns 0 11
12 Unused Int 2 Returns 0 12