Installation Instructions Manual
Publication 1403-IN054B-EN-P - August 2001
B-10 DeviceNet Data Tables
Instance 7 Attributes (Advanced Configuration Data Write)
Assembly Structure
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
3 Set Data Structure of
48 bytes (24 Words)
Param # Parameter name Data type #bytes Master Module Range Default
Setting
Word
No.
1 Password Int 2 0 to 9999 required 0 1
2 Demand period length Int 2 –99 to +99 1 2
3 Number of demand periods Int 2 1 to 15 1 3
4 Output pulse relay # Int 2 0 = None
1 = Relay 1
2 = Relay 2
04
5 Output pulse parameter Int 2 0 = kWh Forward
1 = kWh Reverse
2 = kVarh Forward
3 = kVarh Reverse
05
6 Output pulse increment Int 2 1 to 32766 1 6
7 Output pulse width Int 2 0 or 40 to 2000 100 7
8 Filter mode (1403-MM) Int 2 1 to 3 1 8
9 Restore factory default
config
Int 2 Set to 1 to restore all configuration data
to factory default settings; otherwise
set to 0.
9
10 Clear status input counter #1 Int 2 Set to 1 to clear status input #1 counter;
otherwise set to 0.
(1)
10
11 Clear status input counter #2 Int 2 Set to 1 to clear status input #2 counter;
otherwise set to 0.
(1)
11
12 Clear status input counter #3 Int 2 Set to 1 to clear status input #3 counter;
otherwise set to 0.
(1)
12
13 Clear status input counter #4 Int 2 Set to 1 to clear status input #4 counter;
otherwise set to 0.
(1)
13
14 Clear battery usage timer Int 2 Set to 1 to clear the battery usage timer
to 0; otherwise set to 0.
14
15 Relay #1 Int 2 1=Energize
2=De-energize
4=Remove Force
Set to 0 for no effect on relay #1.
15
16 Relay #2 Int 2 1=Energize
2=De-energize
4=Remove Force
Set to 0 for no effect on relay #2.
16
17 Set W hours Float 4
–9999x10
8
to +9999x10
8
Set to -1.0 for no effect on watt-hour
counter.
17
18