Installation Instructions Manual
Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-9
Instance 6 Attributes (Basic Device Configuration Data Read)
Assembly Structure
Common Services
Attribute
ID
Access
Rule
Name DeviceNet
Data Type
3 Get Data Structure of
40 bytes (20 Words)
Param # Parameter name Data type #bytes Master Module Range Default
Setting
Word No.
1 Present unit password Int 2 PM-II will always return –1 0 1
2 New password Int 2 PM-II will always return –1 0 2
3 Voltage mode Int 2 0 = Demo
1 = Single
2 = Open Delta
3 = 3-Wire Delta
4 = 4-Wire Wye
5 = Direct Delta
43
4 Vaux voltage mode Int 2 0 = AC
1 = DC
04
5 L1/L1/L3 PT primary Float 4 1.0 to 10,000,000.0 120.0 5
6
6 L1/L2/L3 PT secondary Float 4 1.0 to 999.0 120.0 7
8
7 I1/I2/I3 CT primary Float 4 1.0 to 10,000,000.0
1 or 5
(1)
9
10
8 I1/I2/I3 CT secondary Float 4 1.0 to 999.0
1 or 5
a
11
12
9 I4 CT primary Float 4 1.0 to 10,000,000.0
1 or 5
a
13
14
10 I4 CT secondary Float 4 1.0 to 999.0
1 or 5
a
15
16
11 Vaux PT primary Float 4 1.0 to 10,000,000.0 1.0 17
18
12 Vaux PT secondary Float 4 1.0 to 999.0 1.0 19
20
(1) This value will be 1 for 1 Amp Master Module (Cat. No. 1403-MM01X) or 5 for a 5 Amp Master Module (Cat. No. 1403-MM05X)
Service
Code
Service Name
0Ehex Get_Attributes_Single