DeviceNet Data Tables B-95
Instance 5 Attribute (Explicit Client Message Connection
Unused
Common Services
Class 2B - Acknowledge Handler Object
Class Code: 0x2b
Class Attributes
Number of Instances: 1
Instance 1 Attribute
16 Get Consumed Connection
Path
Logical Segment,Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Array of:
USINT 0x20 or 0
0x2B or 0
0x24 or 0
0x01 or 0
0
0
17 Get Production Inhibit Time UINT 0
Attribute ID Access Rule Name DeviceNet Data Value
Service Code Implemented for: Service Name
Class Instance
0x05 Yes Yes
Reset
(1)
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
(1) For "Class", resets all connections to non-existent. For "Instance", resets connection timer, and if applicable changes the state from timed out to
established.
Attribute ID Access
Rule
Name DeviceNet
Data Type
Data Value
1 Get Revision UINT 01
Attribute ID Access Rule Name DeviceNet
Data Type
Data Value
1 Set Acknowledge
Timer
UINT 16 ms (default)
2 Get Retry Limit USINT 1 (default)