Instruction Sheet User guide
General Operation 4-21
1403-IN001A-US-P
Table 4.9 Setpoint Type
Setpoint
Type
Description
0 Not used (inactive)
1 Voltage (any 1 of three phases, L-N in Single
Phase/Wye Modes, L-L in Delta/Open-Delta
Modes)
2 Current (any 1 of three phases)
3 Voltage unbalance
4 Current unbalance
5 Vaux voltage
6 Neutral (I4) current
7 Total kW
8 Total kVAR
9 Total kVA
10 Total true power factor
11 Total displacement power factor
12 Total distortion power factor
13 KW demand
14 KVAR demand
15 KVA demand
16 Current demand
17 Type 1 predictive demand A
18 Type 1 predictive demand W
19 Type 1 predictive demand VAR
20 Type 1 predictive demand VA
21 Type 2 predictive demand A
22 Type 2 predictive demand W
23 Type 2 predictive demand VAR
24 Type 2 predictive demand VA
25 Type 3 predictive demand A
26 Type 3 predictive demand W
27 Type 3 predictive demand VAR
28 Type 3 predictive demand VA
29 Frequency
30 Phase rotation
31
(1)
K-factor: voltage (any 1 of three phases)
32
(1)
K-factor: current (any 1 of three phases)
33
(1)
K-factor: neutral current
34
(1)
Crest factor: voltage (any 1 of three phases)
35
(1)
Crest factor: current (any 1 of three phases)
36
(1)
Crest factor: neutral current
37
(1)
TIF: voltage (any 1 of three phases)
38
(1)
TIF: current (any 1 of three phases)
39
(1)
TIF: neutral current
40 IEEE THD: voltage (any 1 of three phases)
41 IEEE THD: current (any 1 of three phases)
42 IEEE THD: neutral current
43 IEC THD: voltage (any 1 of three phases)
44 IEC THD: current (any 1 of three phases)
45 IEC THD: neutral current
46
(1)
IEEE519: voltage (any 1 of three phases)
47
(1)
IEEE519: current (any 1 of three phases)
48
(1)
IEEE519: neutral current
49 Status input #1
50 Status input #2
51 Status input #3
52 Status input #4
53 Any status input
54 Battery usage timer
(1) Available on 1403-MM only.
Table 4.10 Setpoint Action Type
Setpoint Action
Type
Description
0 No action
1 Energize relay1 and set alarm flag1
2 Energize relay2 and set alarm flag2
3 Set alarm flag3
4 Set alarm flag4
5 Set alarm flag5
6 Set alarm flag6
7 Set alarm flag7
8 Set alarm flag8
9 Set alarm flag9
10 Set alarm flag10
11 Set alarm flag11
12 Set alarm flag12
13 Set alarm flag13
14 Set alarm flag14
15 Set alarm flag15
16 Set alarm flag16
17
1
Initiate oscillograph
18 Perform snapshot
19 Clear kWh power counter
20 Clear kVARh power counter
Table 4.9 Setpoint Type
Setpoint
Type
Description