Maintenance and Troubleshooting 11-9
Excessive Average Current 17 Excessive time at peak cur-
rent
Reduce acceleration rates
Reduce duty cycle (ON/
OFF) of commanded
motion.
Increase time permitted for
motion.
User larger drive and motor.
Software parameter set too
low
Increase Average Current
parameter to a less restric-
tive setting.
Insufficient bus voltage Correct the under voltage
condition or intermittent AC
power or install a larger size
transformer.
Motor Overspeed 18 OVERSPEED parameter in
the drive set to low for the
application
Using ULTRA Master (refer
to Drive Parameters section)
set Overspeed parameter to
an acceptable range for the
application.
Motor commanded to run
above Overspeed setting
Reduce command from
position controller or change
velocity parameter in the
position controller.
Motor Phasing is incorrect Check motor phasing.
Motor encoder phasing is
incorrect
Check encoder phasing.
Excess Following Error 19 Software position error limit
was exceeded
Increase the feed forward
gain to 100%.
Increase the following error
window (refer to
ULTRA Master Drive Param-
eters section).
Retune the drive to reduce
the following error.
Increase the slew limit win-
dow (refer to ULTRA Master
Drive Parameters).
Motor Encoder State Error 20 Motor encoder encountered
an illegal transition
Replace the motor/encoder
Use shielded cables with
twisted pair wires.
Route the feedback away
from potential noise
sources.
Check the system grounds.
Bad encoder Replace motor/encoder.
Table 11.1: Troubleshooting Guide (continued)
Problem or Symptom Error Code Possible Cause(s) Action/Solution