Converting a 300 HP 1397 Drive from 460 to 230 VAC Line Input
Unlike lower horsepower units, 200-300 HP 1397 Drives can be
converted from 460VAC input to 230 VAC input without the use of a
conversion kit. To convert a 300 HP Drive perform the following
steps:
Disconnect and lock out all incoming power to the Drive.
Disconnect the jumpers between H2 and H3 on the control
transformer as shown in Figure 4.3.
Use the jumpers that were removed to connect H1 to H3 and H4
to H2, as shown in Figure 4.3.
Reconnect power to the Drive.
Access parameter 51 [Nominal AC Volt], Set the value to 230.
Converting a 600 HP 1397 Drive from 460 to 230 VAC Line Input
Converting a 600 HP Drive from 460 to 230VAC input is NOT
recommended.
A 600 HP 1397 Drive operating off a 230VAC line input may not
have sufficient voltage for the field supply.