Process PI
[OCL Ramp Time] — P.298
The ramp time for the outer control loop
reference. Sets the minimum amount of time
for the OCL S-curve output to change from 0
to full scale and vice versa. If set to 0.0, the
ramp block is bypassed.
Note: If the ramp block is bypassed, rapid
speed change can result.
Display/Drive Units: SEC
Parameter Type: Tunable
Group: Process PI
Minimum Value: 0.0 sec.
Factory Default: 10.0 sec.
Maximum Value 300.0 sec.
[OCL Reference] — P.299
The reference value for the outer control loop.
Displayed in OCL user units.
Display/Drive Units: CNTS
Parameter Type: Tunable
Group: Process PI
Minimum Value: –4095
Factory Default: 0
Maximum Value 4095