Instruction Manual

582 Programming Parameters
Publication 1397-5.0 June, 2001
Process Display
[Process 1 Par] P.247
This parameter should be set to the number
of the parameter whose scaled value will be
displayed on Line 1 of the HIM Display Panel.
Display/Drive Units: Numeric/Text
Parameter Type: Read & Write
Group: Process Display
Minimum Value: 0
Factory Default: 5
Maximum Value: 308
[Process 1 Scale] P.248
This value sets the scaling multiplier for
[Process 1 Par].
Display/Drive Units: Numeric/Text
Parameter Type: Read & Write
Group: Process Display
Minimum Value: 32768
Factory Default: 1.00
Maximum Value: 32767
[Process 1 Text 1] P.249
Sets the User Units description for the value
determined by [Process 1 Par] and [Process
1 Scale]. The 8 character description will be
shown on line 1 of the display.
Display/Drive Units: Numeric/Text
Parameter Range: Alphanumeric
Parameter Type: Read & Write
Group: Process Display
Minimum Value: 32
Factory Default: 86
Maximum Value: 127
[Process 1 Text 2] P.250
Sets the User Units description for the value
determined by [Process 1 Par] and [Process 1
Scale]. The 8 character description will be
shown on line 1 of the display.
Display/Drive Units: Numeric/Text
Parameter Range: Alphanumeric
Parameter Type: Read & Write
Group: Process Display
Minimum Value: 32
Factory Default: 111
Maximum Value: 127