DIAGNOSTICS
[Logic Status] — P.190
Displays the logic condition. A typical value
at power up would be 0000000000000101
(i.e. drive is ready, not running, forward
direction commanded, no accel/decel, no
alarm, no fault etc.).
Bit Definition Status
0 Enabled 1=Enabled
1 Running 1=Running
2 Command Dir 1=Forward
3 Actual Direction 1=Forward
4 Acceleration 1=Accelerating
5 Deceleration 1=Decelerating
6 Warning 1=Warning
7 Fault 1=Faulted
8 At Ref (speed) 1=At Ref.
9–11 Local #
12–15 Reference *
Display/Drive Units: Numeric/Text
Parameter Range: Bit # Enum Text Bit# Enum Text
0 = Enabled 10 = Local ID
1 = Running 11 = Local ID
2 = Command Dir 12–15 = Reference ID
3 = Actual Dir
4 = Accelerating
5 = Decelerating
6 = Alarm
7 = Faulted
8 = At Speed
9 = Local ID
Group: Diagnostics
Factory Default: 0
Minimum Value: 0
Maximum Value: 15
#
000 = Port 0 local
001 = Port 1 local
010 = Port 2 local
011 = Port 3 local
100 = Port 4 local
110 = Port 5 local
111 = Multiplexed
*
0000 = Master Ext Ref 1 1000 = Master Ext Ref 2
0001 = Int Ref 1 (Preset 1) 1001 = Port 1 Ext Ref
0010 = Int Ref 2 (Preset 2) 1010 = Port 2 Ext Ref
0011 = Int Ref 3 (Preset 3) 1011 = Port 3 Ext Ref
0100 = Int Ref 4 (Preset 4) 1100 = Port 4 Ext Ref
0101 = Int Ref 5 (Preset 5) 1101 = Port 5 Ext Ref
0110 = Int Ref 6 (Preset 6) 1110 = Port 6 Ext Ref
0111 = Int Ref 7 (Preset 7) 1111 = Int Jog
[Drive Status] — P.191
This parameter displays the actual operating
condition in text format
Display/Drive Units: Numeric/Text
Parameter Range: 0 = Not Ready 4 = Tuning
1 = Ready 5 = Stopping
2 = Running 6 = Faulted
3 = Jogging
Group: Diagnostics
Factory Default: 0
Minimum Value: 0
Maximum Value: 6
[AC Line Period] — P.192
Shows AC line as measured by the drive. Display/Drive Units: uSEC
Parameter Type: Read Only
Group: Diagnostics
Factory Default: None
Minimum Value: 16,124
Maximum Value: 20833