OUTPUT CONFIG
[Freq Out Source] P.160
Only used if the I/O Expansion kit is installed.
Selects the signal that drives the frequency
output (terminals 42, 43, and 44 on the I/O
Expansion board). When the frequency
output is at its maximum value, the selected
signal is at its full scale value.
Display/Drive Units: Numeric/Text
Parameter Range: 0 = Cur Lp Fdbk 11 = Arm Volt
1 = Cur Loop Ref 12 = ATach Fdbk
2 = Cur Loop Err 13 = Encoder Fdbk
3 = Spd Loop Fdbk 14 = Zero
4 = Spd Lp Ref 15 = Full Scale
5 = Spd Lp Error 16 = Power Output
6 = Spd Lp Out 17 = OCL Ref
7 = Spd Ramp Out 18 = OCL Ramp Out
8 = Spd Ramp In 19 = OCL Feedback
9 = Spd Src Out 20 = OCL Output
10 = Trim Output 21 = Field Ref
22 = Field Fdbk
Parameter Type: Configurable
Group: Output Config
Factory Default: 14 (Zero)
Minimum Value: 0
Maximum Value: 22
Signal Selected Full Scale Value
[Cur Loop Fdbk] P.006
[Cur Loop Ref] P.008
[Cur Loop Error] P.007
[Spd Loop Output] P.024
[Motor Arm Amps] × Maximum Current
100
[Spd Loop Fdbk] P.022
[Spd Loop Ref] P.025
[Spd Loop Error] P.021
[Spd Ramp Output] P.028
[Spd Ramp Input Tp] P.027
[Spd Sc Output] P.026
[Trim Output] P.030
[Analog Tach Fdbk] P.194
[Encoder Fdbk] P.189
[OCL Output] P.018
Top Speed
[Armature Voltage] P.005 [Motor Arm Volts]
Power Output
[Motor Arm Volts] × [Motor Arm Amps] × Maximum Current
100
[Fld Reference] P.280
[Field Feedback] P.010
[Motor Field Amps]
[OCL Reference TP] P.020
[OCL Ramp Output] P.019
[OCL Feedback] P.017
Full Scale
4095
Zero 0