Instruction Manual

555Programming Parameters
Publication 1397-5.0 June, 2001
OUTPUT CONFIG
[Anlg Out 2 Zero] P.149
Removes any hardware-introduced offset
from the Analog 2 output signal at the
regulator board terminal strip.
Display/Drive Units: Numeric
Parameter Type: Tunable
Group: Output Config
Factory Default: 0
Minimum Value: 200
Maximum Value: 200
[Anlg Out 3 Gain] P.150
Only used if the I/O Expansion kit is installed.
Adjusts analog output 3 (terminals 54 and 55
on the I/O Expansion board) to allow it to
produce a signal from 5.0 to approximately
13.0 V DC.
Display/Drive Units: VDC
Parameter Type: Tunable
Group: Output Config
Factory Default: 1.00
Minimum Value: 0.500
Maximum Value: 1.300
This is typically used to adjust the 10 V full scale output to match the input voltage requirement of attached equipment. For example, this
parameter would be set to 0.800 to match the requirements of equipment that accepts a 0 to 8 V DC signal.
The outputs are only rated to 10 V DC, so gain adjust values greater than 1.000 might cause the analog output circuit to saturate.