Instruction Manual

547Programming Parameters
Publication 1397-5.0 June, 2001
INPUT CONFIG
[Anlg In 1 Gain] P.127
Used to scale the analog input 1 signal after it
has been conditioned by the drive hardware.
Typically, it will be 1.000.
Display/Drive Units: Numeric
Parameter Type: Tunable
Group: Input Cong
Factory Default: 1.000
Minimum Value: 0.750
Maximum Value: 2.250
[Anlg In 1 Type] P.128
Selects the analog input 1 signal type.
Note: Jumpers J10 and J12 must be set for
the same type of signal selected by this
parameter.
Display/Drive Units: Numeric
Parameter Range: 0 = 0-10V
1 = ±10V
2 = 4 -20mA
3 = 10-50mA
Parameter Type: Configurable
Group: Input Config
Factory Default: 0
Minimum Value: 0
Maximum Value: 3
[Anlg In 1 Zero] P.129
Used to remove any hardware introduced
offset from the analog auto reference signal.
Typically, it will be 0.
Display/Drive Units: Numeric
Parameter Type: Tunable
Group: Input Config
Factory Default: 0
Minimum Value: 200
Maximum Value: 200
[Anlg In 2 Gain] P.130
Scales the manual mode analog reference
signal after it has been conditioned by the
drive hardware. Typically, it will be 1.000.
Display/Drive Units: Numeric
Parameter Type: Tunable
Group: Input Config
Factory Default: 1.000
Minimum Value: 0.750
Maximum Value: 2.250