Instruction Manual

546 Programming Parameters
Publication 1397-5.0 June, 2001
FEATURE SELECT
[Trim Reference] P.120
Drive register to manually set the trim
reference value used by the drive.
Display/Drive Units: %
Parameter Range: ±100.0%
Parameter Type: Tunable
Group: Feature Select
Factory Default: 0
Minimum Value: 100%
Maximum Value: +100%
[OCL Enable Src] P.121
Sets the source of the OCL enable signal.
Register means it comes from [OCL
Enable]. Terminal Blk means I/O Expansion
#64.
Display/Drive Units: Numeric/Text
Parameter Range: 0 = Register
1 = Terminal Blk
Group: Feature Select
Parameter Setting: Tunable
Factory Default: 0
Minimum Value: 0
Maximum Value: 1
[Inertia Comp Reg] P.122
Allows inertia compensation value to be
entered (via Datalink also) when Inertia Comp
Src P. 102 is set to Register. The value of
this parameter is not saved through a
powercycle, it is reset to zero at powerup.
Display/Drive Units: CNTS Counts
Parameter Range: 0 4095
Group: Feature Select
Parameter Setting: Tunable
Factory Default: 0
Minimum Value: 0
Maximum Value: 4095