Instruction Manual

535Programming Parameters
Publication 1397-5.0 June, 2001
REFERENCE SET
[Preset Speed 1, 2 and 3] P.87, P.88 and P.89
These parameters set up to three preset
speed references when the Regulator Type
jumper (J15 on the regulator board) is set for
the speed/voltage control loop or current
reference when J15 is set to current.
Display/Drive Units: %FLA
Parameter Range: 0 to [Maximum Current] %FLA
Default Setting: 150 %FLA
Parameter Type: Tunable
Group: Reference Set
Display/Drive Units: RPM
OR
Parameter Range: [Min Process Speed] to [Max Process Speed] RPM
Default Setting: 250 RPM
Parameter Type: Tunable
Group: Reference Set
Factory Default: 250
Minimum Value: Min Process Speed
Maximum Value: Max Process Speed
[Ref 1 Source] P.090
Selects the source of external reference 1 Display/Drive Units: Numeric/Text
Parameter Range: 0 = Anlg In 1
1 = Speed Pot
2 = MOP Output
3 = Anlg In 3
4 = Anlg In 4
5 = Frequency In
6 = Adapter 1
7 = Adapter 2
8 = Adapter 3
9 = Adapter 4
10 = Adapter 5
11 = Adapter 6
12 = Preset 1
13 = Preset 2
14 = Preset 3
Parameter Type: R & W
Group: Reference Set
Factory Default: 0
Minimum Value: 0
Maximum Value: 14