530 Programming Parameters
Publication 1397-5.0 June, 2001
ADV SETUP
[Cur Loop RateLim] P.064
Minimum allowable time for selected Current
Loop reference to change from zero to
[Maximum Current].
Display/Drive Units: MSEC
Parameter Type: Tunable
Group: Advanced Setup
Factory Default: 40
Minimum Value: 1.000
Maximum Value: 100
[IR Compensation] P.066
Sets the armature voltage compensation
value used when the drive is configured as a
voltage regulator. This parameter is also used
by the field current regulator to set the field
weakened threshold.
Display/Drive Units % [Motor Arm Volts (P046)]
Group: Advanced Setup
Factory Default: 0
Minimum Value: 0
Maximum Value: 50%
[Pos Current Lim] P.067
Sets the highest amount of current (% motor
rated armature amps) for the forward bridge.
Used as a high limit for the speed loop PI
block output.
Display/Drive Units: % FLA
Parameter Type: Tunable
Group: Advanced SetUp
Factory Default: 150%
Minimum Value: 0
Maximum Value: Max Setting of Param 040
Note: Setting of this parameter is limited by the setting of
Parm 040.
[Neg Current Lim] P.068
Note: This parameter is only set for
regenerative drives.
Selects the highest amount of current (%
motor rated armature amps) for the reverse
bridge. Used as a low limit for the Speed
Loop PI block output.
Display/Drive Units: % FLA
Parameter Type: Tunable
Group: Advanced Setup
Factory Default: 150%
Minimum Value: 0
Maximum Value: 200%