Instruction Manual

16 Introduction
Publication 1397-5.0 June, 2001
Full Load Rated
RMS AC Line
Current (Amperes)
Full Load Rated
DC Armature
Current (Amperes)
Rated Field Current
(Amperes)
Power Source
Capacity
1
(Amperes)
Minimum
Source
HP
230 V AC
460 V AC 240 V DC 500 V DC 150 VDC 300 V DC 230 V AC 460 V AC
So
u
rce
kVA
1.5 10 - 7 - 10 - 5000 - 4
2 11 - 9 - 10 - 5000 - 5
3 13 10 12 6 10 10 5000 5000 6
5 19 12 20 10 10 10 5000 5000 7.5
7.5 26 15 29 14 10 10 5000 5000 11
10 33 18 38 19 10 10 5000 5000 15
15 48 24 55 27 10 10 5000 5000 20
20 63 31 73 35 15 10 10000 5000 27
25 80 39 93 45 15 10 10000 5000 34
30 94 45 110 52 15 10 10000 5000 40
40 125 63 146 73 15 15 25000 10000 51
50 154 74 180 86 15 15 25000 10000 63
60 186 86 218 100 15 15 25000 10000 75
75 226 110 265 129 15 15 25000 25000 93
100 307 143 360 167 15 25000 118
125 370 177 434 207 15 25000 145
150 443 213 521 250 15 25000 175
200 281 330 15 30000 220
250 351 412 15 30000 275
300 421 495 15 30000 330
400 567 667 15 75000 440
500 680 800 15 75000 550
600 816 960 15 75000 660
ATTENTION: When applying 1397 Drives to a power distribution system with KVA capacity in excess of five times the smallest
drive rating the use of an isolation transformer or line reactors of similar impedance is required. Also, the Drives are designed
for a maximum of three units per transformer.
1 Maximum permissible available symmetrical RMS fault current.
380 VAC
KW/HP
415 VAC
KW/HP
380/415
Full Load Rated
RMS AC Line
Current Amperes
380/415
Full Load Rated
DC Armature
Current Amperes
Rated
Field
Current
Power
Source
Capacity
(Amperes)
1.8/2.4 2.1/2.8 10 7 10 5,000
9/12 10.3/13.6 26 29 10 5,000
17.9/24 20.6/27.6 48 55 10 5,700
35.8/48 41.2/55.2 94 110 15 11,500
89.5/120 102.9/138 226 265 15 25,000
Power Ratings and Supply
Capacity (230/460VAC)
Power Ratings and Supply
Capacity (380/415VAC)