Chapter 4
Installation
4-7
Table 4.B
Rack Setup Switch Settings (U5)
Description SSW7 SW8
Full Rack X X
Physical Rack Size = 3
Starting Quarter = 0
Last Rack = 1
Half Rack – Top (1) X ON
Physical Rack Size = 1
Starting Quarter = 2
Last Rack = 1
Half Rack – Bottom, Last (1) ON X
Physical Rack Size = 1
Starting Quarter = 0
Last Rack = 1
Half Rack – Bottom, Not Last ON ON
Physical Rack Size = 1
Starting Quarter = 0
Last Rack = 0
(1) IMPORTANT: When using the PLC 5/15 or 5/25, the following series and software revisions
are required as a minimum.
Series Revision
PLC 5/15 B J
PLC 5/25 A E
X = OFF or Open
ON = Closed
Table 4.C
Baud Rate Setting (U6)
Baud Rate SW 1
57.6kbps ON
115.2kbps X
Table 4.D
Termination Resistor Setting (U6)
Resistor SW 4
Connected ON
Not Connected X