Manual
Chapter 4
Installation
4-6
Table 4.A
Rack Address Switch Settings (U5)
Rack# SW 1 SW 2 SW 3 SW 4 SW 5 SW 6
00 ON ON ON ON ON ON
01 ON ON ON ON ON X
02 ON ON ON ON X ON
03 ON ON ON ON X X
04 ON ON ON X ON ON
05 ON ON ON X ON X
06 ON ON ON X X ON
07 ON ON ON X X X
10 ON ON X ON ON ON
11 ON ON X ON ON X
12 ON ON X ON X ON
13 ON ON X ON X X
14 ON ON X X ON ON
15 ON ON X X ON X
16 ON ON X X X ON
17 ON ON X X X X
20 ON X ONONONON
21 ON X ON ON ON X
22 ON X ON ON X ON
23 ON X ON ON X X
24 ON X ON X ON ON
25 ON X ON X ON X
26 ON X ON X X ON
27 ON X ON X X X
30 ON X X ON ON ON
31 ON X X ON ON X
32 ON X X ON X ON
33 ON X X ON X X
34 ON X X X ON ON
35 ON X X X ON X
36ONXXXXON
37ONXXXXX
(1) IMPORTANT: When using the PLC 5/15 or 5/25, the following series and software revisions
are required as a minimum.
Series Revision
PLC 5/15 B J
PLC 5/25 A E
X = OFF or Open
ON = Closed