Owner manual

Chapter 3
Control Description
3-2
Table 3.A
Configuration
Parameters
Port
A
Port B Name Function
400 300 Digital Input Fast Source, Discrete Input to Drive
401 301 Analog In 1 Fast Source, Analog 1 Input to Drive
402 302 Analog In 2 Fast Source, Analog 2 Input to Drive
403 303 Analog In 3 Fast Source, Analog 3 input to Drive
404 304 Analog In 4 Fast Source, Analog 4 Input to Drive
450 350 Digital Output Fast Sink, Discrete Output from Drive
451 351 Analog Out 1 Fast Sink, Analog 1 Output from Drive
452 352 Analog Out 2 Fast Sink, Analog 2 Output from Drive
453 353 Analog Out 3 Fast Sink, Analog 3 Output from Drive
454 354 Analog Out 4 Fast Sink, Analog 4 Output from Drive
Table 3.B
SetUp
Parameters
Program Terminal Units Internal Units
Port A Port B Description Default Range Default Range
550 500 ADC Scale 1 1 (-16, 16) 2048 ± 32767
551 501 ADC Offset 1 0 (-20, 20) 0 ± 4096
552 502 ADC Scale 2 1 (-16, 16) 2048 ± 32767
553 503 ADC Offset 2 0 (-20, 20) 0 ± 4096
554 504 ADC Scale 3 1 (-16, 16) 2048 ± 32767
555 505 ADC Offset 3 0 (-20, 20) 0 ± 4096
556 506 ADC Scale 4 1 (-16, 16) 2048 ± 32767
557 507 ADC Offset 4 0 (-20, 20) 0 ± 4096
558 508 Digital Out 1 10 at Zero Spd (0,15) 10 0 - 15
559 509 Digital Out 2 5 Drive Running (0,15) 5 0 - 15
560 - 574 510 - 524 Not Used
575 525 DAC Scale 1 1 (-1,1) 32767 ± 32767
576 526 DAC Offset 1 0 (-20, 20) 0 ± 4096
577 527 DAC Scale 2 1 (-1, 1) 32767 ± 32767
578 528 DAC Offset 2 0 (-20, 20) 0 ± 4096
579 529 DAC Scale 3 1 (-1, 1) 32767 ± 32767
580 530 DAC Offset 3 0 (-20, 20) 0 ± 4096
581 531 DAC Scale 4 1 (-1, 1) 32767 ± 32767
582 532 DAC Offset 4 0 (-20, 20) 0 ± 4096
583 (1) 533 (1) Digital In 1 11 Stop (0,15) 11 0 - 15
584 534 Digital In 2 9 Jog 2 (0,15) 9 0 - 15
585 535 Digital In 3 12 Start (0,15) 12 0 - 15
586 536 Digital In 4 14 Drv Flts (0,15) 14 0 - 15
587 - 598 537 - 548 Not Used
599 549 Adapter Board Identifier 3.xx -
(1) Digital In 1 is designed for use with a Normally Closed (NC) operator device. Applying positive control voltage to Digital In 1
(Terminal TB3 - 48) will cause the bit specified to be set to zero. With no voltage applied to Digital In 1, the bit will be one.