Instruction Manual

720 Programming
Feature Select
[Slip Comp Gain]
This parameter is the gain for the slip compensation and
adjusts the recovery rate after a load change.
Parameter Number 195
Parameter Type Read and Write
Display Units / Drive Units None
Factory Default 1
Minimum Value 1
Maximum Value 40
[Run On Power Up]
This parameterenables the function thatallows the drive
to automatically restart on Power Up. This parameter
requiresthatatwowirecontrolschemebeinstalledatTB4-
TB6andthatavalidstartcontactbepresent.RefertoInput
Mode Selection in Chapter 3 or 4.
Parameter Number 14
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
[Reset/Run Tries]
This value sets the maximum number of times the drive
attemptstoresetafaultandrestartbeforethedriveissues
a“MaxRetriesFault”.SeeChapter8foralistofresettable
faults.
Parameter Number 85
Parameter Type Read and Write
Display Units / Drive Units 1 Try / Tries
Factory Default 0
Minimum Value 0
Maximum Value 9
[Reset/Run Time]
This value sets the time between restart attempts when
[Reset/Run Tries] is set to a value other than zero.
Parameter Number 15
Parameter Type Read and Write
Display Units / Drive Units 0.1 Second / Seconds x 100
Factory Default 1.0 Sec
Minimum Value 0.5 Sec
Maximum Value 30.0 Sec
[S Curve Enable]
This parameter enables the fixed shape S curve accel/
decelramp.Programmedaccel/deceltimesaredoubledif
[S CurveTime] is setto “0”.An adjustableS curve willbe
created if [S Curve Time] is greater than zero.
Parameter Number 57
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
[S Curve Time]
This createsan adjustables curveramp.If S CurveTime
is<theprogrammedaccel/deceltime,theactualrampwill
bethesumofthetwo.IfSCurveTimeistheprogrammed
accel/decel times, a fixed S curve will be created whose time
is double the programmed accel/decel time.
Parameter Number 56
Parameter Type Read and Write
Display Units / Drive Units 0.1 Second / Seconds x 10
Factory Default 0.0 Sec
Minimum Value 0.0 Sec
Maximum Value 1800.0 Sec
ATTENTION: ThisparametermayonlybeusedasoutlinedinNFPA79,“Under
VoltageProtection.Equipmentdamageand/orpersonalinjurymayresultifthis
parameter is used in an inappropriate application.
!