Instruction Manual
7–6 Programming
Metering
[Encoder Freq]
Not available.
Parameter Number 63
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value –400.00 Hz
Maximum Value +400.00 Hz
[Pulse Freq] – Stand-Alone Version Only
Thisparameter displaysthe frequencycommandpresent
at the pulse input terminals. This value is displayed
whether or not this is the active frequency command.
Parameter Number 254
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value –400.00 Hz
Maximum Value +400.00 Hz
[MOP Freq] – Stand-Alone Version Only
Thisparameterdisplaysthefrequencycommandfromthe
MOP. The MOP frequency command can be adjusted by
TB5&TB6(ifpresent)andappropriateinputsareselected
(see page
3–5 or 4–5). Some SCANport adapters,
including the RIO Adapter, can also adjust the MOP
frequency command. This value is displayed whether or
not this is the active frequency command.
Parameter Number 137
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Heatsink Temp]
This parameter displays the heatsink temperature of the
drive.
Parameter Number 70
Parameter Type Read Only
Display Units / Drive Units 1° C / Deg. C
Factory Default None
Minimum Value 0
Maximum Value 255° C
[Power OL Count]
Displays the percentage of accumulated I
2
t for the drive
thermal overload protection. Running continuously above
131%ofdriveratedampswillaccumulateavalueof100%and
generate a Power Overload Fault (F64).
Parameter Number 84
Parameter Type Read Only
Display Units / Drive Units 1 % / 4096 = 100%
Factory Default None
Minimum Value 0%
Maximum Value 200%
[Motor OL Count]
This parameter displays the percentage of accumulated
I
2
t for the motoroverload protection. Running continuously at
programmed[OverloadAmps] willaccumulate approximately
70%.Reduction ofload willreduce theOL count.100% value
will generate an Overload Fault (F07).
Parameter Number 202
Parameter Type Read Only
Display Units / Drive Units 1 % / 4096 = 100%
Factory Default None
Minimum Value 0%
Maximum Value 200%
[Last Fault]
This parameter displays the last drive fault. It is updated
whenever a new fault occurs.
Parameter Number 4
Parameter Type Read Only
Display Units / Drive Units Fault Number / Fault Number
Factory Default None
Minimum Value None
Maximum Value None
Frequency
Displayed
Incoming Pulse Rate (Hz)
[Pulse Scale]
=