Instruction Manual
Programming 7–5
Metering
Thisgroupofparametersconsists ofcommonlyvieweddriveoperatingconditionssuch as
motor speed,driveoutput voltage, currentand commandfrequency. All parameters inthis
group are Read Only and can only be viewed.
[Output Current]
This parameter displays the output current present at
terminals U, V & W (T1, T2 & T3).
Parameter Number 54
Parameter Type Read Only
Display Units / Drive Units 0.1 Amp / 4096 = 100% Drive Rated Amps
Factory Default None
Minimum Value 0.0
Maximum Value 200% Rated Drive Output Current
[Output Voltage]
Thisparameterdisplaysthecommandedoutputvoltageat
terminals U, V & W (T1, T2 & T3).
Parameter Number 1
Parameter Type Read Only
Display Units / Drive Units 1 Volt / 4096 = 100% Drive Rated Volts
Factory Default None
Minimum Value 0
Maximum Value 200% Rated Drive Output Voltage
[Output Power]
This parameter displays the output power present at
terminals U, V & W (T1, T2 & T3).
Parameter Number 23
Parameter Type Read Only
Display Units / Drive Units 1 kilowatt / 4096 = 100% Drive Rated kW
Factory Default None
Minimum Value –200% Rated Drive Output Power
Maximum Value +200% Rated Drive Output Power
[DC Bus Voltage]
This parameter displays the DC bus voltage level.
Parameter Number 53
Parameter Type Read Only
Display Units / Drive Units 1 Volt / 4096 = 100% Drive Rated Volts
Factory Default None
Minimum Value 0
Maximum Value 200% DC Bus Voltage Max
[Output Freq]
This parameter displays the output frequency present at
terminals U, V & W (T1, T2 & T3).
Parameter Number 66
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default None
Minimum Value –400.00 Hz
Maximum Value +400.00 Hz
[Freq Command]
This parameter displays the frequency that the drive is
commandedtooutput.Thiscommandmaycomefromany
one of the frequency sources selectedby [Freq Select 1]
or [Freq Select 2].
Parameter Number 65
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default None
Minimum Value –400.00 Hz
Maximum Value +400.00 Hz
[Anlg In 0 Freq] – Stand-Alone Version Only
[Anlg In 1 Freq] – Stand-Alone Version Only
[Anlg In 2 Freq] – Stand-Alone Version Only
These parameters displays the frequency command
presentatthespecifiedanaloginputterminals.Thisvalue
is displayed whether or not this is the active frequency
command.
Parameter Number 138-140
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz