Instruction Manual

Start-Up 67
5. Set [Maximum Freq] and [Maximum Voltage] parameters to correct values
(typically line voltage/frequency). Set [Base Voltage] and [Base Frequency]
parameters to the motor nameplate values.
A. Fromthe Status Display, presstheEnterkey (oranykey).“Choose Mode”
will be displayed.
B. Press the Increment (or Decrement) key until “Program” is displayed.
C. Press Enter.
D. Press the Increment key until “Setup” is displayed.
E. Press Enter.
F. PresstheIncrementorDecrementkeysuntil“MaximumFreq”isdisplayed.
Press SELect. The first character of line 2 will now flash.
G. UsetheIncrement/Decrementkeystodisplaythefirstdigit,thenpressEnter.
Repeat for remaining digits.
H. Repeat the above steps to program the remaining parameters located in
the Motor Control group.
I. Press the ESCape key (3 times) to return to the Status Display.
Choose Mode
EEProm
Choose Mode
Program
Metering
Setup
Input Mode
3 Wire
Maximum Freq
60
Stopped
+0.00 Hz
Choose Sensorless
Vector or V/Hz
6. Sensorless Vector or V/Hz (Volts/Hertz) operation.
Sensorless Vector or Volts/Hertz operation is selectable via [Control Select].
Vector operationis thedefault. IfV/Hz operationis desired,reprogram [Control
Select] using the steps above as a programming guide. Refer to Chapter 7.
Important: For synchronous motors, use Volts/Hertz operation.
Advanced Start-Up Procedure
Press these keys . . . while following these steps . . . The HIM Display will show . . .
or
or
or &
or &