Instruction Manual
Start-Up 6–5
Advanced Start-Up This procedure is designed for complex applications requiring a
more detailed start-up.
Advanced Start-Up Procedure
Press these keys . . . while following these steps . . . The HIM Display will show . . .
Disconnect Motor 1. Remove thedrivecoverand disconnectthe motorleads fromterminalsU,V,W
(T1, T2 and T3).
Apply Power 2. Apply AC power and control voltages to the drive. The LCD Display should
light and display adrivestatusof “Stopped”and anoutputfrequency of“+0.00
Hz.”
If the drive detects a fault, a brief statement relating to the fault will be shown
on the display. Record this information, remove all power and correct the fault
source before proceeding. Refer to Chapter 8 for fault descriptions.
Stopped
+0.00 Hz
Reset Factory Defaults
3. Important: Theremaining stepsinthisprocedure arebasedonfactorydefault
parameter settings. If the drive has been previously operated, parameter
settings may have beenchanged andmay not becompatible with thisstart-up
procedure or application. Drive status and fault conditions may be unpredict-
able when power is first applied.
To obtain proper results, the parameters must be restored to factory default
settings.Afterrestoring tofactory defaults, several parametersmust beinitially
set as explained below.
A. From the Status Display, press Enter (or any key). “Choose Mode” will be
displayed.
B. Press the Increment (or Decrement) key until “EEPROM” is displayed. If
EEProm is not in themenu, programming is password protected. Refer to
Chapter 5 for Password information.
C. Press Enter.
D. PresstheIncrement(orDecrement)keyuntil“ResetDefaults”isdisplayed.
E. Press Enter to restore all parameters to their original factory settings.
F. Press ESC. “Reprogram Fault” will display, indicating successful reset.
G. Press the Stop key to reset the fault. Refer to page A–12 and program
parameters 36, 242-244. Cycle power.
Choose Mode
Display
Choose Mode
EEProm
EEProm
Reset Defaults
Choose Mode
EEProm
Reprogram Fault
F48
Stopped
+0.00 Hz
or
or