Instruction Manual
Start-Up 6–3
Reset Factory Defaults
2. Important: Theremaining stepsin thisprocedure arebased onfactory default
parameter settings. If the drive has been previously operated, parameter
settings may havebeenchangedandmay notbe compatible withthis start-up
procedure or application. Drive status and fault conditions may be unpredict-
able when power is first applied.
To obtain proper results, the parameters must be restored to factory default
settings.After restoringtofactorydefaults,severalparametersmustbe initially
set as explained below.
A. From the Status Display, press Enter (or any key). “Choose Mode” will be
displayed.
B. Press the Increment (or Decrement) key until “EEPROM” is displayed. If
EEProm is notin the menu, programming is password protected.Refer to
Chapter 5 for Password information.
C. Press Enter.
D. PresstheIncrement(orDecrement)keyuntil“ResetDefaults”isdisplayed.
E. Press Enter to restore all parameters to their original factory settings.
F. Press ESC. “Reprogram Fault” will display, indicating successful reset.
G. Press the Stop key to reset the fault. Refer to page A–12 and program
parameters 36, 242-244. Cycle power.
Choose Mode
Display
Choose Mode
EEProm
EEProm
Reset Defaults
Choose Mode
EEProm
Reprogram Fault
F48
Stopped
+0.00 Hz
3. From the StatusDisplay, press the Enter key (or any key). “Choose Mode” will
be displayed.
A. Press the Increment (or Decrement) key until “Startup” is displayed.
B. Press Enter.
Important: All questions can be answered Yes or No. Pressing Enter will
select the default (“Y” or “N”). Pressing the Increment (or Decrement) key will
change the selection – press Enter to select. Choosing “Y” allows you to pro-
ceed through the step, “No” will advance you to the next step. In addition, the
following should be noted:
• The“Startup”modecanbeexitedatanytimebypressingESCapeuntilthe
StatusDisplayisshown. Ifyouwishto re-enterthe “Startup” mode,simply
select “ResetSequence” tostart fromthebeginning.Selecting “Continue”
allows you to resume from the point where you left off.
• Completingthelastactioninanystepwillautomaticallytakeyoutothenext
step.
• Pressing SELect will activate line 2 of the display – this must be done for
all values.
• Press the Increment (or Decrement) key to adjust a value (skip if value is
correct).PressEntertostorethevalueorretaintheexistingvalue.Pressing
Enter again will cause you to move to the next step (parameter).
Choose Mode
Display
Choose Mode
Startup
Assisted Start-Up
Keys Description The HIM Display will show . . .
or
or
or
or