42 Installation/Wiring for PLC Control Drives
Cable Routing
If unshielded cable is used, signal circuits should not run parallel to
motor cables or unfiltered supply cables with a spacing less than 0.3
meters (1 foot). Cable tray metal dividers or separate conduit should
be used.
Important: When user installed control and signal wiring with an
insulationrating oflessthan 600Vis used,thiswiring must
be routed inside the drive enclosure and separated from
any other wiring and/or uninsulated live parts.