Instruction Manual

34 Installation/Wiring for Stand-Alone Drives
Circuits must be capable of operating with high = true logic.
DC external circuits in the low state must generate a voltage of no
more than 8V DC. Leakage current must be less than 1.5 mA into a
2.5k ohm load.
DC external circuits in the high state must generate a voltage of +20
to +26 volts and source a current of approximately 10 mA for each
input. The stand-alone version is compatible with these
Allen-Bradley PLC modules:
1771-OB 1771-OQ16 1771-OB16
1771-OBD 1771-OYL
1771-OBN 1771-OZL
1771-OQ 1771-OBB
The 24 volt power supply is capable of supplying a total of 16 digital
inputs.
Typical
2019 21 22 23 24 25
0.22
µ
f
1k
20k
510
510 510
26 27 28 29 30
TB4 TB5 TB6 TB7
24V Common
24V
Contacts shown are general, refer to Input Mode Select and information presented above.