2–12 General Installation for All Drives
How to Measure Motor Cable Lengths Limited by Capacitance
Table 2.E
Maximum Motor Cable Length Restrictions in meters (feet) - 380V-480V Drives
1
This current is only possible with synchronous motors and for spinning applications. For actual motor current rating, refer to Appendix A.
Output Devices Drive Output Disconnection
180 (590)
15 (50)
15 (50) 15 (50)
90 (295)
90 (295)
165 (540)
All examples represent motor cable length of 180 meters (590 feet).
150 (490)
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
Drive Catalog
Number
Peak
Current
Rating
1
Cable
Diameter
mm
2
(AWG)
No External Devices 1321-3R55-A Reactor at Drive 1321-3R25-A Reactor at Drive
Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
220-240V AC 800V 1000V 1200V 800V 1000V 1200V
1336Z- _ A022 21.6A 2.5 (12) 120 (394) 120 (394) 120 (394) 180 (590) 180 (590) 180 (590)
1336Z- _ A036 36.0A 2.5 (12) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590)
1336Z- _ A060 60.0A 6.0 (8) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590)
380-400V AC 1000V 1200V 1400V 1000V 1200V 1400V 1000V 1200V 1400V
1336Z- _ B010 9.9A 2.5 (12) 15 (50) 105 (344) 105 (344) 30 (98) 180 (590) 180 (590) 60 (197)
1336Z- _ B017 16.5A 2.5 (12) 15 (50) 115 (377) 115 (377) 30 (98) 180 (590) 180 (590) 60 (197)
1336Z- _ B033 33.0A 6.0 (8) 15 (50) 155 (509) 180 (590) 30 (98) 180 (590) 180 (590) 60 (197)
460-480V AC 1200V 1400V 1600V 1200V 1400V 1600V 1200V 1400V 1600V
1336Z- _ B010 9.9A 2.5 (12) 15 (50) 105 (344) 105 (344) 30 (98) 180 (590) 180 (590) 60 (197)
1336Z- _ B017 16.5A 2.5 (12) 15 (50) 115 (377) 115 (377) 30 (98) 180 (590) 180 (590) 60 (197)
1336Z- _ B033 33.0A 6.0 (8) 15 (50) 120 (394) 180 (590) 30 (98) 180 (590) 180 (590) 60 (197)
!
ATTENTION: To guard against drive damage, always dis-
able thedrive beforedisconnecting the motorfrom the drive
output terminals. Any disconnecting means wired to the
drive output terminals U, V and W must be capable of dis-
abling the drive if opened during drive operation. If opened
(motor disconnected) during drive operation, the drive will
continue to produce output voltage between U, V, & W
(drive damage could occur). An auxiliary contact must be
used to simultaneously disable the drive.