Instruction Manual

Specications and Supplemental Information A3
Power Dissipation
Derating Guidelines Drive ratings can be affected by a number of factors. If more than one
factor exists, derating percentages must be multiplied.
Shading indicates Drive [Rated Amps], “ * ” Indicates No Overload.
1
For 20 seconds every 10 minutes. The maximum [Current Limit] setting is shown.
2
The maximum [Current Limit] setting is shown. Normal Duty (ND) = 100%, 110% for 1 minute to 10
minutes, peak current for 3 seconds.
3
Note that parameter 13, [DC Hold Level] must NOT be set to 150%, but maximum as follows:
(A022) 140%, (A036) 140%, (A060) 100%, (B010) 70%, (B017) 70%, (B033) 70%.
4
The dynamicbraking currentis onlydefined bythe externalresistor. Thereis nointernal currentcontrol
norshortcircuitprotection.Respectivemeasures asbimetal relay,klixonetchavetobetakenexternally.
5
See Chapter 2 fordynamic brake resistor wiring information andAppendix B for dimension information.
Voltage
Catalog
Number
Peak
Current
Carrier Frequency, 50 Degree C Ambient
2 kHz 4 kHz 8 kHz
Cont.
Current
Power Dissipation Formula
I
L
= RMS Load Current
Cont.
Current
Power Dissipation Formula
I
L
= RMS Load Current
Cont.
Current
Power Dissipation Formula
I
L
= RMS Load Current
200-240V 1336Z-xA022 21.6A 9.0A P=29W+(I
L
x 4.4V)+(I
2
L
x 0.17) 9.0A P=29W+(I
L
x 4.9V)+(I
2
L
x 0.17) 9.0A P=29W+(I
L
x 5.4V)+(I
2
L
x 0.17)
1336Z-xA036 36.0A 15.0A P=33W+(I
L
x 4.4V)+(I
2
L
x 0.10) 14.0A P=33W+(I
L
x 4.9V)+(I
2
L
x 0.10) 10.0A P=33W+(I
L
x 5.4V)+(I
2
L
x 0.10)
1336Z-xA060 60.0A 30.0A P=40W+(I
L
x 4.4V)+(I
2
L
x 0.05) 25.0A P=40W+(I
L
x 4.9V)+(I
2
L
x 0.05) 18.0A P=40W+(I
L
x 5.4V)+(I
2
L
x 0.05)
380-480V 1336Z-xB010 9.9A 8.5A P=29W+(I
L
x 5.5V)+(I
2
L
x 0.36) 5.5A P=29W+(I
L
x 7.8V)+(I
2
L
x 0.36)
1336Z-xB017 16.0A 10.0A P=33W+(I
L
x 5.5V)+(I
2
L
x 0.22) 6.0A P=33W+(I
L
x 7.8V)+(I
2
L
x 0.22)
1336Z-xB033 33.0A 17.0A P=40W+(I
L
x 5.5V)+(I
2
L
x 0.11) 10.0A P=40W+(I
L
x 7.8V)+(I
2
L
x 0.11)
Voltage
Rating
Drive
Catalog
No.
Carrier
Frequency
Synch./Synch. Reluctance Motors Induction Motors
DCBrake
Current
3
DynamicBrake
Current
4,5
F.L.A. Current Limit
1
F.L.A. Current Limit
2
kHz Ta=50˚C Ta=45˚C Ta=40˚C Peak Current Ta=50˚C Ta=45˚C Ta=40˚C Peak Current at 0 Hz A
rms
A
DC
/R
min
200-240V A022 2 9A 9A 9A 21.6A = 240% 9A 9A 9A 14.4A = 160% 160% 12.6 15A/25 Ohms
49A9A9A 9A9A9A
89A9A9A 9A9A9A
A036 2 15A 15A 15A 36A = 240% 13.9A 15A 15A 24A = 160% 118% 21.0 15A/25 Ohms
4 14A 15A 15A 13A 15A 15A
8 10A 12.5A 15A 11A 13.6A 15A
A060 2 30A 30A 30A 60A = 200% 24A 28.2A 30A 48A = 160% 101% 30.0 23A/16 Ohms
4 25A 30A 30A 23A 26.5A 30A
8 18A 22A 26A 18A 23.8A 27A
380-480V B010 2 8.5A 9.9A 9.9A 9.9A = 100% 8.5A 9.9A* 9.9A* 9.9A = 100% 89% 7.0 10A/75 Ohms
4 5.5A 6.4A 7.3A 5.5A 8.4A 9.9A*
B017 2 10.0A 11.5A 13.0A 16.5A = 127% 9.5A 11.6A 13A 16.5A = 127% 105% 9.1 14A/53 Ohms
4 6.0A 7.2A 8.4A 6.0A 9.6A 11.1A
B033 2 17A 20A 23A 33A = 143% 16.8A 19.9A 23A 33A = 143% 101% 16.1 17A/43 Ohms
4 10A 12A 14A 14A 16.5A 19A
Altitude
% of Drive
Rated Amps
Altitude
m
(ft)
100%
80%
90%
0 4,000
(13,200)
3,000
(9,900)
2,000
(6,600)
1,000
(3,300)
Altitude All Drive Ratings