Instruction Manual

A2 Specications and Supplemental Information
Electrical
Input Data
Voltage Tolerance: –50% of maximum (with reduced output power),
+10% of maximum.
Frequency Tolerance: 47-63 Hz.
Input Phases: Three-phase input provides full rating for all drives.
Displacement Power Factor 0.97 standard, value is application dependent.
Efficiency: 97.5% at rated amps, nominal line volts.
Max. Short Circuit Current Rating:
Using Specified Fuses 200,000A
Total Harmonic Distortion (THD): acc. IEEE519/EEN61800-3
Control
Method: Sine coded PWM with programmable carrier frequency. Ratings
apply to all drives (refer to the Derating Guidelines on page A–3).
200-240V AC Drives 2, 4, 8 kHz.
380-480V AC Drives 2, 4 kHz.
Output Voltage Range: 0 to rated voltage.
Output Frequency Range: 0 to 400 Hz.
Frequency Accuracy
Digital Input: Within ±0.01%of maximum output frequency.
Analog Input: Within ±0.4% of maximum output frequency.
Selectable Motor Control: Sensorless Vector with full tuning. Standard V/Hz with full custom
capability.
Accel/Decel: Twoindependentlyprogrammableaccel anddeceltimes.Eachtime
may be programmed from 0 - 3600 seconds in 0.1 second
increments
1
.
Intermittent Overload: Variable Overload (see Drive Ratings).
Current Limit Capability: Proactive CurrentLimit programmablefrom 20% topeak current of
ratedoutputcurrent.Independentlyprogrammableproportionaland
integral gain.
Inverse Time Overload Cap. Class 10 protection with speed sensitive response. Investigated by
U.L.tocomplywithN.E.C.Article430.U.L.FileE59272,volume4/6.
1
0.1 second increments using a HIM or 0.01 with serial communications.
Input/Output Ratings
Note: Drive ratings are at nominal values. See Derating Guidelines on
page A–3.
2
Values based on line source, kVA = 10 x Drive Output kVA.
Drive
Catalog No.
1336Z- . . .
Synchronous Reluctance Motor
cosϕ = 0.6
Input Amps
2
Output kVA Output Amps
200-240V DRIVES
xA022
xA036
xA060
7.6
12.5
24.6
3.7
6.2
12.5
9.0
15.0
30.0
380-480V DRIVES
xB010
xB017
xB033
8.7
11.4
19.8
8.2
10.8
19.1
9.9
13.0
23.0