Instruction Manual
7–48 Programming
Process
Display
Thisgroup ofparameterscontainsthe parametersusedto scale,in“User Units”,anydrive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.
[Process 1 Par]
This parameter should be set to the number of the
parameterwhosescaled valuewillbe displayedon Line1
of the HIM Display Panel.
The maximum process value that can be displayed is
99,999.99. If thisvalue is exceeded, a character string of
asterisks (****) will appear on the display.
Parameter Number 127
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 1
[Process 1 Scale]
This value sets the scaling multiplier for [Process 1 Par].
The displayed value will be:
Parameter Number 128
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value –327.68
Maximum Value +327.67
[Process 1 Txt 1-8]
Setsthe“UserUnits”descriptionforthe valuedetermined
by[Process1Par]and[Process1Scale].This8character
description willbe shownon line1 of thedisplay. Referto
the Character Map in Appendix A.
Parameter Number(s) 129-136
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default “Volts ”
[Process 2 Par]
This parameter should be set to the number of the
parameterwhosescaled valuewillbe displayedon Line2
of the HIM Display Panel.
The maximum process value that can be displayed is
99,999.99. If thisvalue is exceeded, a character string of
asterisks (****) will appear on the display.
Parameter Number 180
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 54
[Process 2 Scale]
This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:
Parameter Number 181
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value –327.68
Maximum Value +327.67
[Process 2 Txt 1-8]
Setsthe“UserUnits”descriptionforthe valuedetermined
by[Process2Par]and[Process2Scale].This8character
description willbe shownon line2 of thedisplay. Referto
the Character Map in Appendix A.
Parameter Number(s) 182-189
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default “Amps ”
[Process 1 Par] actual value
x [Process 1 Scale] value
Displayed Value
[Process 2 Par] actual value
x [Process 2 Scale] value
Displayed Value