Instruction Manual
Programming 7–37
Diagnostics
[Drive Alarm 2]
This parameter displays which alarm
conditionis presentwhen bit6 of[Drive
Status 1] ishigh. Referto Chapter 8 for
further alarm information.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number 269
Parameter Type Read Only
[Latched Alarms 1]
Thisparameter“stores”the[DriveAlarm
1] indications (see above). Bits will
remain set (high/1), even if the alarm
condition no longer exists. The bit(s)
mustbe programmedto zero torelease
the stored indications.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number 205
Parameter Type Read Only
[Latched Alarms 2]
Thisparameter“stores”the[DriveAlarm
2] indications (see above). Bits will
remain set (high/1), even if the alarm
condition no longer exists. The bit(s)
mustbe programmedto zero torelease
the stored indications.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number 270
Parameter Type Read Only
[Input Status]
This parameter displays the on/off status of inputs 1-8 at
TB4-TB6 if an optional interface card is installed.
A Status description (bit ENUM) is displayed on line 1
(except Series A HIMs below version 3.0).
Parameter Number 55
Parameter Type Read Only
Motor Therm
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Phase Loss
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Motor Therm
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input 1 - TB4-19
Input 2 - TB5-20
Input 4 - TB5-23
Input 3 - TB5-22
Input 5 - TB5-24
Input 6 - TB6-26
Input 8 - TB6-28
Input 7 - TB6-27