Instruction Manual
Programming 7–35
Faults
[Fault Alarms 2]
This parameter storesand displays the
last alarm conditions present prior to a
fault.RefertoChapter8forfurtheralarm
information.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number 287
Parameter Type Read Only
[Flt Clear Mode]
This parameter controls the method for clearing faults.
Parameter Number 39
Parameter Type Read and Write
Factory Default “Enabled”
Units Display Drive
“Disabled” 0 Faults cleared only by cycling power
“Enabled” 1 Faultsclearedbyissuingavalidstop
command(onlythroughTB5/HIM)or
cycling power - refer to Bit 3 of the
LogicControlStructureonAppendix
A.
[Ground Warning]
Enables the Ground Warning fault (F57) when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 8 for further information.
Parameter Number 204
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0 No Fault Generated
“Enabled” 1 Ground Warning Generated
[Phase Loss Mode]
Enables the function that detects a phase loss or the
current rating has been exceeded in the drive if powered
on single-phase line. A fault (F49) or alarm condition will
occur if the DC bus ripple voltage exceeds the level in
[Phase Loss Level].
Parameter Number 330
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0 No Fault Generated
“Alarm” 1 Generates a Phase Loss Alarm
“Fault” 2 Generated F49 Input Phase Fault
[Phase Loss Level]
SetstheDCbusripple voltageabovewhichaphase loss
fault/alarmwilloccur.Thesensitivityfordetectingablown
fuse on a three-phase system can be increased by
lowering the setting for this parameter.
Parameter Number 331
Parameter Type Read and Write
Display Units / Drive Units 0.1 Volts / 4096 = Drive Rtd Volts
Factory Default 9.0/18.0/22.5 Volts
Minimum Value 5.1/10.1/12.7 Volts
Maximum Value 22.5/45.0/56.2 Volts
[Precharge Fault]
Enablesor disables thePrecharge Fault, which indicates
insufficient DC bus charging 20 seconds after power-up.
Parameter Number 332
Parameter Type Read and Write
Factory Default “Enabled”
Units Display Drive
“Disabled” 0 No Fault Generated
“Enabled” 1 Precharge Fault Generated
Motor Therm
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check